STRATHCONA POOL (STR104) - BUILDING CONDITION ASSESSMENT REPORT

20 Sep 2022

As indicated in the body of the report, most of the spalling bricks on the exterior have been fenced off from public access with the exception of the staff entrance on the north side. [...] The exterior slab on the west side appears to be settling and moving, this is likely due to a combination of water ingress along the side of the building affecting the subgrade beneath these slabs along with the vegetation in the area. [...] The overall condition of the building mechanical systems is marginal; however, the condition of the pool process equipment is critical as the boiler and heat exchanger were not operational. [...] This Repaint 2032 $3,300 handrails at the sides and middle of the stairs in appears well-maintained and repainted within the the basement corridor connecting the pool to the last five to ten years. [...] The transformer is not the responsibility of the property and is owned by the utility so no budget is included.